- What we need from you
- Plans, sections and ceiling layout; the ventilation design with terminal positions and air volumes; diffuser types where known; equipment, furniture and heat gains; and the criteria the room has to meet.
- What you get
- Temperature, velocity and humidity plots on planes and probe lines, a compliance table against each criterion, comparison of design options, and a report stating the inputs, boundary conditions and limits of the model.
- How long it takes
- Fee proposal within 1 working day; we confirm the programme with the proposal.
Which CFD Study Does Your Project Need?
Controlled rooms with a written specification. Laboratories, clean spaces, server rooms and other controlled environments often come with limits on temperature, temperature gradient, air speed, humidity or room pressure. CFD tests the ventilation design against each limit and reports the results in a compliance table, so the design team can see which pass and what to change before installation.
Air distribution and comfort. Supply and extract positions, diffuser throw, draught at desks and seating, dead zones and short-circuiting between supply and extract. Useful for offices, meeting rooms, classrooms and any space where occupants have complained or the layout has changed.
Stratification in tall spaces. Whether warm air from high-level heaters or fan coil units reaches the occupied zone in warehouses, stores, sports halls, atria and production spaces, and how racking or mezzanines change the air path.
Entrances, doors and air curtains. How far cold air travels through an open door, the air speed and temperature at a reception desk, whether cold air reaches connected spaces, and how much an air curtain reduces it.
Comparing design options. Different diffuser positions, supply temperatures, terminal unit layouts or door arrangements, run on the same grid and boundary conditions so the comparison is like for like.
If you are not sure whether CFD is needed, send us the question the design team is trying to answer and we will tell you which method suits it.
How We Run CFD
Boundary conditions from a dynamic model. We run the building in ApacheSim, find the design hours (such as summer peak and winter minimum), and import the internal surface temperatures and gains into MicroFlo. The CFD then reflects the real fabric and weather at those hours rather than assumed wall temperatures.
The room as designed. Supply diffusers, extract grilles and their air volumes come from the ventilation drawings. Equipment, benches and racking are added as solid obstructions, with heat and moisture sources where they apply. Room pressurisation is modelled from the supply and extract imbalance with a pressure boundary at the door or leakage path.
Temperature, humidity and pressure. MicroFlo carries moisture as well as heat, so relative humidity can be checked against a target alongside temperature and air speed.
Steady state and time together. MicroFlo is a steady-state solver: it models one moment with conditions settled. Where stability over an hour or a day matters, or a door opens repeatedly, we pair the CFD worst cases with a dynamic simulation of the same room to show how far conditions drift and how quickly they recover.
What the Report States
A CFD image is only as reliable as the inputs behind it. Every report sets out the grid and how mesh independence was checked, the turbulence model, the boundary conditions, how airflows were calibrated and the convergence criteria. Results that do not meet a criterion are shown, not left out. Where a model is too coarse for comfort criteria, such as a whole-building overview, it is labelled as indicative.