This article covers school and college buildings in England procured under the DfE's employer's requirements, Technical Manual revision C01, dated 12 January 2026. The gov.uk link for the older Output Specification daylight annex (Annex 2E) now leads to the same page as the Technical Manual. If your contract or brief still names Annex 2E, work to the edition it names: the thresholds are familiar but the pass rule is different, as set out below.
The two criteria
| Criterion | What is measured | Required |
|---|---|---|
| Daylight autonomy, sDA(300/50%) | Percentage of the task plane that receives at least 300 lux for at least 50% of annual occupied hours | At least 50% |
| Useful daylight illuminance, UDI-a (100 to 3000 lux) | Percentage of occupied hours that the illuminance at each grid point is between 100 and 3000 lux | Average of at least 80% across the space |
Source: DfE Technical Manual, January 2026, section 5.8.7.
They are different kinds of result. sDA counts grid points: each point passes or fails, and half of them have to pass. UDI-a is an average of every point's score.
That is why a room can meet one and fail the other. A deep room with a low window head can stay above 100 lux at the back for most of the day, and meet UDI-a, without reaching 300 lux over half the task plane. A room with a lot of unshaded glass can meet sDA easily and fail UDI-a, because the points near the window spend too many hours above 3000 lux.
Which rooms must meet which criterion
| Space | sDA 50% | UDI-a 80% |
|---|---|---|
| General teaching, practical and ICT-rich spaces | Yes | Yes |
| Science and D&T spaces, prep rooms | Yes | Yes |
| Staff social rooms, staff workrooms, continuously occupied offices | Yes | Yes |
| Halls, dining areas, libraries (LRCs) | No | Yes |
| Toilets and changing rooms with external walls, kitchens, reception areas, corridors, stairs | Own external windows and/or rooflights | |
| Store rooms, hygiene rooms, plant rooms | Daylight access not required | |
Source: DfE Technical Manual, January 2026, section 5.8.7.
Where an SEN classroom cluster has a small group room or one to one room opening directly off the teaching space, the two are modelled as one space, with no partition between them.
What changed from Annex 2E
We compared the Technical Manual with the May 2020 edition of Annex 2E. The sDA and UDI-a thresholds for basic teaching spaces are the same. The pass rule isn't.
Annex 2E (May 2020) asked for 80% of basic teaching spaces, counted by number of rooms, to meet the primary criteria. The rest had to come as close as possible. The Technical Manual gives no percentage: all of the listed spaces "shall meet" the criteria. The exception is overshadowing. Where a space is overshadowed and can't meet the requirements, the team has to demonstrate that daylight has been optimised in that space.
Time steps changed too: 15 minutes maximum in Annex 2E, less than one hour in the Technical Manual.
The model settings
| Input | Requirement |
|---|---|
| Weather file | EnergyPlus Weather (EPW) file nearest to the site |
| Calculation method | Radiosity or ray tracing, with at least 5 light bounces for ray tracing |
| Time increments | Less than 1 hour |
| Occupied hours | 08:30 to 16:00 |
| Geometry | Main structural elements, window fenestration and external obstructions |
| Trees and planting | Not included in the final compliance model |
| Surface reflectance | The proposed wall, floor and ceiling finishes |
| Walls | Area-weighted, assuming 20% of the surface is covered with items at 0.2 reflectance |
| Desks | Reflectance accounted for |
| Grid | Points to within 500 mm of the walls, 250 to 500 mm apart |
| Dirt on surfaces | Manufacturer's reflectance reduced by 10% |
| Dirt on glazing | Manufacturer's light transmittance reduced by 5% |
Source: DfE Technical Manual, January 2026, sections 5.8.1 and 5.8.8.
The working plane follows the task heights in Table 22 of the manual:
| Space | Task height, m |
|---|---|
| Primary basic teaching areas, primary libraries | 0.55 |
| Secondary general teaching, music, SEN and support spaces, art studios, libraries (LRC), study areas | 0.75 |
| Technology and science classrooms | 0.85 |
| Dining and social areas, staff areas | 0.75 |
| Halls and indoor PE spaces, sports halls | 0 (floor level) |
Source: DfE Technical Manual, January 2026, Table 22.
The reflectance reductions add up. As an illustration, a wall paint with a stated reflectance of 0.70 drops to 0.63 after the 10% reduction, and to 0.54 once 20% of the wall is taken as 0.2. Glazing with a stated light transmittance of 0.70 is modelled at 0.665.
Where daylight conflicts with other requirements
Four other clauses in the manual pull against the daylight result:
- G-value. Maximum 0.4 for glazed elements facing east, west and south (section 2.6.6). Solar control glass usually has a lower light transmittance than clear glass, so check both figures for the same product.
- Brise soleil. Horizontal external shading is required on windows within 45° of due south (section 0.1.3). It belongs in the daylight model as well as the overheating model.
- Rooflights. They must be positioned to limit solar gain and glare, for example not over the performance area of a hall or the marked courts of a sports hall (section 2.3.28).
- Finishes. The minimum light reflectance value is 50% for walls (3.1) and 70% for ceilings (3.3), unless natural materials are used. Floors must be between 5% and 40% (3.2). These are limits for the specification; the daylight model uses the finishes actually proposed.
Blinds are needed on exterior glazing in all occupied spaces, apart from clerestory windows used for ventilation where blackout isn't needed. Where roller blinds control solar glare, the weave openness must not exceed 3%, with a visible light transmittance of 5 to 7% (section 4.1.28). Section 5.8.8 doesn't give a blind schedule for the daylight model, so agree with the DfE's technical adviser whether the runs assume blinds open.
What has to be reported
The Integrated Environmental Design Report must set out how daylight has been optimised throughout the building, for approval by the Employer's Representative (section 5.8.7). Room-by-room sDA and UDI-a results are the core of that. For any overshadowed room, show the options that were tested and why the final one is the best available.
Before you run the model: a checklist
- Confirm which document the contract names: the 2026 Technical Manual or an earlier Annex 2E.
- List every room against the space types above, and mark which criteria apply.
- Get the glazing specification with both g-value and light transmittance for the same product.
- Get the proposed wall, floor and ceiling reflectance values, then apply the 10% reduction and the 20% display allowance to the walls.
- Model the brise soleil, window reveals, frames and neighbouring buildings. Leave trees out of the final run.
- Set the working plane by room type from Table 22, and the grid to within 500 mm of the walls.
- Run sDA and UDI-a together with the overheating model, before the window sizes are fixed.